DF2410 Integral Valve & Actuator
DF2410 Fail Closed Front View
previous
next

DF2410 Integral Valve & Actuator

Heavy duty, compact control valve.

  • 1 and 2 inch NPS (25 and 50mm DN) Valve
  • 1/4 to 1-1/4 inch (6.4 to 31.8mm) Port
  • Globe and Angle Body Styles
  • RF |  RTJ  |  FNPT Available End Connections
  • ASME B16.34 Class 150 to 1500 Pressure Rating
  • ANSI/FCI 70.2 and IEC 60534-4 Class IV Shutoff
More Details

DF2410 integral control valves are rugged and designed for demanding tight-space applications. The compact design makes installation and maintenance more convenient than traditional valve and actuator assemblies while offering the same functionality.

Overview

DF2410 Integral Valve & Actuator

  • Standard live-loaded packing

  • Hammer nut bonnets

  • NACE construction standard

Product Specifications

DF2410 Available ConfigurationsOpen arrow
AVAILABLE CONFIGURATIONS
BODY SIZE END CONNECTION
FNPT RF (FLANGED CONNECTION) RTJ (FLANGED CONNECTION)
ASME CLASS 150 ASME CLASS 300 ASME CLASS 600 ASME CLASS 900/1500 ASME CLASS 600 ASME CLASS 900/1500
  2" NPS (50mm DN) ü ü ü ü ü ü ü
  NOTES: FNPT = 2,250 PSI (155 BAR) COLD WORKING PRESSURE.
DF2410 Available Shutoff ClassificationsOpen arrow
AVAILABLE SHUTOFF PRESSURE DROPS WITH COMMON INSTRUMENTATION
ACTUATOR ACTION FLOW DIRECTION (PRESSURE TENDS TO) PORT DIAMETER TYPE OF ACTUATOR SPRING
LIGHT SPRING HEAVY SPRING
0-18 PSIG (0-1.24 BARG) OPERATING PRESSURE 0-20 PSIG (0-1.38 BARG) OPERATING PRESSURE 0-30 PSIG (0-2.07 BARG) OPERATING PRESSURE 0-33 PSIG (0-2.28 BARG) OPERATING PRESSURE 0-35 PSIG (0-2.41 BARG) OPERATING PRESSURE 0-50 PSIG (0-3.45 BARG) OPERATING PRESSURE
FAIL CLOSED FLOW UP (OPENS VALVE) 1/4" (6.4mm) 3,750 PSI (259 BAR) 3,750 PSI (259 BAR) 3,750 PSI (259 BAR) 3,750 PSI (259 BAR) 3,750 PSI (259 BAR) 3,750 PSI (259 BAR)
3/8" (9.5mm) 3,750 PSI (259 BAR) 3,750 PSI (259 BAR) 3,750 PSI (259 BAR) 3,750 PSI (259 BAR) 3,750 PSI (259 BAR) 3,750 PSI (259 BAR)
1/2" (12.7mm) 2,765 PSI (191 BAR) 2,765 PSI (191 BAR) 3,180 PSI (219 BAR) 3,750 PSI (259 BAR) 3,750 PSI (259 BAR) 3,750 PSI (259 BAR)
3/4" (19.1mm) 1,160 PSI (80 BAR) 1,160 PSI (80 BAR) 1,340 PSI (92 BAR) 1,785 PSI (123 BAR) 2,080 PSI (143 BAR) 2,080 PSI (143 BAR)
1" (25.4mm) 610 PSI (42 BAR) 610 PSI (42 BAR) 715 PSI (49 BAR) 965 PSI (67 BAR) 1,130 PSI (78 BAR) 1,130 PSI (78 BAR)
1-1/4" (31.8mm) 365 PSI (25 BAR) 365 PSI (25 BAR) 430 PSI (30 BAR) 590 PSI (41 BAR) 700 PSI (48 BAR) 700 PSI (48 BAR)
FAIL OPEN FLOW UP (OPENS VALVE) 1/4" (6.4mm) 3,750 PSI (259 BAR) 3,750 PSI (259 BAR) 3,750 PSI (259 BAR) 3,750 PSI (259 BAR) 3,750 PSI (259 BAR) 3,750 PSI (259 BAR)
3/8" (9.5mm) 3,750 PSI (259 BAR) 3,750 PSI (259 BAR) 3,750 PSI (259 BAR) 3,750 PSI (259 BAR) 3,750 PSI (259 BAR) 3,750 PSI (259 BAR)
1/2" (12.7mm) 2,715 PSI (187 BAR) 3,380 PSI (233 BAR) 3,750 PSI (259 BAR) 3,750 PSI (259 BAR) 3,750 PSI (259 BAR) 3,750 PSI (259 BAR)
3/4" (19.1mm) 1,135 PSI (78 BAR) 1,430 PSI (99 BAR) 2,130 PSI (147 BAR) 2,575 PSI (178 BAR) 2,875 PSI (198 BAR) 3,750 PSI (259 BAR)
1" (25.4mm) 600 PSI (41 BAR) 765 PSI (53 BAR) 1,160 PSI (80 BAR) 1,410 PSI (97 BAR) 1,575 PSI (109 BAR) 2,830 PSI (195 BAR)
1-1/4" (31.8mm) 355 PSI (24 BAR) 465 PSI (32 BAR) 715 PSI (49 BAR) 875 PSI (60 BAR) 985 PSI (68 BAR) 1,785 PSI (123 BAR)
NOTES: (1) When using an instrument such as a positioner or controller with a 3-15 PSI (0.21-1.05 BAR) input signal use the 0 to 20 PSIG column (Light Spring).
(2) For valve use where downstream pressure exceeds 2,750 PSIG (190 BARG), 2,750 PSIG should be used as the Maximum Shut-off Pressure.
(3) Do not exceed the Pressure Temperature Limitations as per ASME B16.34.
                 
AVAILABLE SHUTOFF PRESSURE DROPS WITH RESTRICTED OUTPUT RANGE INSTRUMENTATION
ACTUATOR ACTION PORT DIAMETER TYPE OF ACTUATOR SPRING
HEAVY SPRING
6-30 PSIG (0.41-2.07 BARG) OPERATING PRESSURE
FAIL CLOSED 1/4" (6.4mm) 3,750 PSI (259 BAR)
3/8" (9.5mm) 3,045 PSI (210 BAR)
1/2" (12.7mm) 1,635 PSI (113 BAR)
3/4" (19.1mm) 655 PSI (45 BAR)
1" (25.4mm) 330 PSI (23 BAR)
1-1/4" (31.8mm) 185 PSI (13 BAR)
FAIL OPEN 1/4" (6.4mm) 3,750 PSI (259 BAR)
3/8" (9.5mm) 3,750 PSI (259 BAR)
1/2" (12.7mm) 2,845 PSI (196 BAR)
3/4" (19.1mm) 1,195 PSI (82 BAR)
1" (25.4mm) 630 PSI (43 BAR)
1-1/4" (31.8mm) 380 PSI (26 BAR)
NOTES: (1) Instrument Example: for a Electro-Pneumatic Transducer calibrated for 6 to 30 PSIG (0.41 to 2.07 BARG).
(2) For fail closed valve use where downstream pressure exceeds 1,715 PSIG (118 BARG), 1,715 PSIG should be used as the Maximum Shut-off Pressure.
(3) For fail open valve use where downstream pressure exceeds 2,750 PSIG (190 BARG), 2,750 PSIG should be used as the Maximum Shut-off Pressure.
(4) Do not exceed the Pressure Temperature Limitations as per ASME B16.34.
DF2410 Available Flow CharacteristicsOpen arrow
CHARACTERISTIC PREFERRED FLOW DIRECTION
EQUAL PERCENTAGE REFER TO SHUT OFF PRESSURE DROPS

DF2410 Control Valve Documentation

DF2410 Instruction Manual - Fail Closed
Dynaflo, DynaFlo, Integral Valve & Actuator, Manuals & Software
DF2410 Sales Bulletin
Dynaflo, DynaFlo, Integral Valve & Actuator, Manuals & Software
Refer to our FloSpec software for product selection, sizing and ordering

Refer to our FloSpec software for product selection, sizing and ordering

This site uses cookies to improve our service, you can find out more here - for the best web experience please accept cookies

x